3 pc

3 monitor
Product Specs
-
True double-conversion
-
Output power factor 0.8
-
Wide input voltage range (110-300 VAC)
-
Input power factor correction 0.98
-
50/60 Hz frequency converter mode
-
ECO mode operation for energy saving (ECO)
-
Programmable power management outlet
-
Emergency power off (EPO) function
-
Generator compatible
-
SNMP+USB+RS-232 multiple communications (Options)
-
Smart battery charger design for optimized battery performance
-
Selectable output voltage,
Product Details
|
CAPACITY |
1000 VA / 800 W | |||||
|
INPUT | ||||||
|
Voltage Range |
Low Line Transfer |
160 VAC / 140 VAC / 120 VAC / 110 VAC ± 5 % or 80 VAC / 70 VAC / 60 VAC / 50 VAC ± 5 % ( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0) | ||||
|
Low Line Comeback |
175 VAC ± 5 % veya 85 VAC ± 5 % | |||||
|
High Line Transfer |
300 VAC ± 5 % veya 150 VAC ± 5 % | |||||
|
High Line Comeback |
290 VAC ± 5 % veya 145 VAC ± 5 % | |||||
|
Frequency Range |
40Hz ~ 70 Hz | |||||
|
Phase |
Single phase with ground | |||||
|
Power Factor |
≧ 0.95 | |||||
|
OUTPUT | ||||||
|
Output voltage |
220 VAC | |||||
|
AC Voltage Regulation (Batt. Mode) |
± 3% | |||||
|
Frequency Range (Synchronized Range) |
47 ~ 53 Hz veya 57 ~ 63 Hz | |||||
|
Frequency Range (Batt. Mode) |
50 Hz ± 0.25 Hz veya 60Hz ± 0.3 Hz | |||||
|
Overload |
100%~110%: audible warning 110%-130%: UPS shuts down in 30 seconds at battery mode or transfers to bypass mode when the utility is normal. >130%: UPS shuts down immediately at battery mode or transfer to bypass mode when the utility is normal. | |||||
|
Current Crest Ratio |
3:1 | |||||
|
Harmonic Distortion |
≦ 3 % THD (Linear Load) | |||||
|
Transfer Time |
AC Mode to Batt. Mode |
0 | ||||
|
Inverter to Bypass |
4 ms (Typical) | |||||
|
Waveform (Batt. Mode) |
Pure Sinewave | |||||
|
EFFICIENCY | ||||||
|
AC Mode |
~ 85% | |||||
|
Battery Mode |
~ 83% | |||||
|
BATTERY | ||||||
|
Standard Model |
Battery Type |
12 V / 7 AH | ||||
|
Numbers |
3 | |||||
|
Recharge Time |
4 hours recover to 90% capacity (Typical) | |||||
|
Charging Current |
1.0 A( max.) | |||||
|
Charging Voltage |
82.1 VDC ±1% | |||||
|
Long-run Model |
Battery Type & Numbers |
Depending on the capacity of external batteries | ||||
|
Charging Current |
4.0 A veya 8.0 A(max.) | |||||
|
Charging Voltage |
82.1 VDC ±1% | |||||
|
PHYSICAL | ||||||
|
Dimension, D X W X H |
421 X 190 X 318 | |||||
|
Net Weight (kgs) |
28 | |||||
|
ENVIRONMENT | ||||||
|
Operation Humidity |
20-90 % RH @ 0- 40°C (non-condensing) | |||||
|
Noise Level |
Less than 45dBA @ 1 Meter | |||||
|
MANAGEMENT | ||||||
|
Smart RS-232 or USB |
Windows® 98/2000/2003/XP/Vista/2008, Windows® 7, Linux, and MAC | |||||
|
Optional SNMP |
Power management from SNMP manager and web browser | |||||