Product Specs
-
True double-conversion
-
Output power factor 0.8
-
Wide input voltage range (110-300 VAC)
-
Input power factor correction 0.98
-
50/60 Hz frequency converter mode
-
ECO mode operation for energy saving (ECO)
-
Programmable power management outlet
-
Emergency power off (EPO) function
-
Generator compatible
-
SNMP+USB+RS-232 multiple communications (Options)
-
Smart battery charger design for optimized battery performance
-
Selectable output voltage,
Product Details
|
CAPACITY |
10000 VA / 8000 W | |||||||
|
INPUT | ||||||||
|
Voltage Range |
Low Line Loss |
110 VAC ± 3 % at 50% Load; 176 VAC ± 3 % at 100% Load | ||||||
|
Low Line Comeback |
Low Line Loss Voltage + 10V | |||||||
|
High Line Loss |
300 VAC ± 3 % | |||||||
|
High Line Comeback |
High Line Loss Voltage - 10V | |||||||
|
Frequency Range |
46Hz ~ 54 Hz @ 50Hz system 56Hz ~ 64 Hz @ 60Hz system | |||||||
|
Phase |
Single phase with ground | |||||||
|
Power Factor |
≧ 0.99 at 100% Load | |||||||
|
OUTPUT | ||||||||
|
Output voltage |
208/220/230/240VAC | |||||||
|
AC Voltage Regulation |
± 1% | |||||||
|
Frequency Range (Synchronized Range) |
46Hz ~ 54 Hz @ 50Hz system 56Hz ~ 64 Hz @ 60Hz system | |||||||
|
Frequency Range (Batt. Mode) |
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz | |||||||
|
Overload |
AC Mode |
100%~110%: 10min 110%~130%: 1min >130% : 1sec | ||||||
|
Battery Mode |
100%~110%: 30sec 110%~130%: 10sec >130% : 1sec | |||||||
|
Current Crest Ratio |
3:1 max | |||||||
|
Harmonic Distortion |
≦ 3 % @ 100% Linear Load; ≦ 6 % @ 100% Non-linear Load | |||||||
|
Transfer Time |
AC Mode to Batt. Mode |
0 ms | ||||||
|
Inverter to Bypass |
0 ms | |||||||
|
Inverter to ECO |
<10 ms | |||||||
|
Waveform (Batt. Mode) |
Pure Sinewave | |||||||
|
EFFICIENCY | ||||||||
|
AC Mode |
> 89% | |||||||
|
Battery Mode |
> 88% | |||||||
|
BATTERY | ||||||||
|
Standard Model |
Battery Type |
12 V / 9 Ah | ||||||
|
Numbers |
20 | |||||||
|
Recharge Time |
9 hours recover to 90% capacity | |||||||
|
Charging Current |
1.0 A ± 10% (max.) | |||||||
|
Charging Voltage |
14.4 V ± 1% | |||||||
|
Long-run Model |
Battery Type & Numbers |
Depending on the capacity of external batteries | ||||||
|
Charging Current |
4.0 A ± 10% (max.) | |||||||
|
Charging Voltage |
14.4 V ± 1% | |||||||
|
PHYSICAL | ||||||||
|
Outline |
Dimension, D X W X H |
592 X 250 X 576 | ||||||
|
Net Weight (kgs) |
83 |
27 | ||||||
|
Packaging |
Dimension, D X W X H |
700 X 385 X 815 |
690 X370 X670 | |||||
|
Net Weight (kgs) |
90 |
30 | ||||||
|
ENVIRONMENT | ||||||||
|
Operation Humidity |
<95 % and non-condensing | |||||||
|
Noise Level |
Less than 58dB @ 1 Meter | |||||||
|
MANAGEMENT | ||||||||
|
Smart RS-232 or USB |
Windows® 98/2000/2003/XP/Vista/2008, Windows® 7, Linux, and MAC | |||||||
|
Optional SNMP |
Power management from SNMP manager and web browser | |||||||
Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC.
If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.
Product specifications are subject to change without further notice.